TD800 Series Large Screen Temperature Display

TD800 series large-screen temperature displayer is an intelligent temperature displayer, which is a display supporting instrument for infrared pyrometer or other detector instruments.
Retail price
0.0
Market price
0.0
观看次数:
1000
编号
Quantity
-
+
Stock:
0
Details

1. Product introduction

TD800 series large-screen temperature displayer is an intelligent temperature displayer, which is a display supporting instrument for infrared pyrometer or other detector instruments. Using dot matrix red LED scanning display, compared with ordinary methods, power consumption is lower. The displayed pixels are accurate to each pixel, and even individual damage will not affect the entire display. It can be hung on the wall, clearly visible within 100 meters, and the display is intuitive and convenient.

It can arbitrarily modify the range setting, signal processing functions include peak value, Valley value, and average value. And according to user needs, the average temperature within a period of time can be retained, and automatically updated when the next temperature arrives. With instrument self-check function and accuracy correction function.

 

2. Technical parameters

Working power supply

AC220(1±20%)V, with EMI filter

Input signal

4mA~20mA, sampling resistance 100 ohm, with overvoltage protection, overcurrent protection

Measurement accuracy

±0.2%tm℃(tm is the upper limit of temperature measurement range)

Repeat accuracy

±1℃

The upper limit corresponds to the temperature

Setting range is -50℃~3200℃, upper limit temperature corresponds to 20mA

The lower limit corresponds to the temperature

Setting range is -50℃~3200℃, lower limit temperature corresponds to 4mA

Measurement mode

Real-time temperature: setting time is 0.0s, response time is 10ms

Peak temperature: Set time from 0s to 99.9s, >99.0s is infinite hold.

Valley temperature: Set time from 0s to 99.9s, >99.0s is infinite hold.

Average temperature: setting time 0s~60.0s, average response time
For the time it takes for the signal to rise to 95%, a first-order RC algorithm is used.

Correction coefficient

Setting range is 990~1010, and the coefficient is 1000 without calibration

Average
Trigger function

User can choose to turn it on or off, and can set the upper limit and lower limit of the trigger temperature.
The upper/lower limit temperature setting range is -50℃~3000℃.
Automatically maintain the previous average temperature of the target.

Display self-calibration function

Display "88.88℃", used for LED light-emitting tube test.

Power-down protection function

When power is off, the values ​​of various setted parameters will be retained

Alarm function

User can set the upper and lower limit alarm threshold .
And there is corresponding relay output, node capacity 5A/250VAC

Using environment

Ambient temperature: -10℃~60℃, relative humidity: 10~95%, no condensation

Power consumption

Without alarm: 6W (all LEDs on)
With alarm: 16W (LEDs are all on and the alarm is activated at the same time), the alarm is optional

Dimensions

Length, width and height (500mm*168mm*65mm)

 

3. Wiring instruction

(1) TD800-2 Wiring Table

1

2

3

4

5

6

7

mA+

mA-

AL+

AL-

DC24V

0V

Shield

(4-20)mA
Current input

Alarm output

DC24V/500mA output

Shielding layer

 

(2) TD800-1 Wiring Table

1

2

7

mA+

mA-

Shield

(4~20)mA current input

Shielding layer

 

 

(3) Power input wiring table

L

N

Earth

FireWire

Zero line

The Earth

AC220V power input

3-core plug cord, with a cord length of 3m, a wire diameter of 1 square

 

4. Outline drawing of large-screen displayer